Set |
FDUA100VNP1VF2 |
Indoor |
FDUA100VF2 |
Outdoor |
FDC100VNP |
Power supply |
Outdoor Unit |
|
1 Phase 230V 50Hz |
Capacity |
Cooling T1 |
kW |
10.0 (2.8-11.2) |
Heating H1 |
11.2 (2.5-12.5) |
Input |
Cooling T1 |
kW |
2.99 |
Heating H1 |
2.88 |
Max running current |
|
A |
21 |
EER |
Cooling T1 |
|
3.34 |
COP |
Heating H1 |
3.89 |
Sound pressure level (JIS C9612) |
Indoor |
dB
(A) |
P-Hi:43 Hi:42
Me:40 Lo:37 |
Outdoor |
57 |
Sound power level (JIS C9612) |
Outdoor |
dB(A) |
70 |
Airflow |
Indoor |
l/s |
P-Hi:650 Hi:600
Me:550 Lo:483 |
External static pressure |
|
Pa |
200 |
External dimensions (HXWXD) |
Indoor |
mm |
398x1150x650 |
Outdoor |
845x970x370 |
Net weight |
Indoor |
kg |
52 |
Outdoor |
70 |
Refrigerant piping |
Liquid line |
mm |
Ø9.52 |
Gas line |
Ø15.88 |
Connection method |
|
Flare Connection |
Refrigerant R410A |
Quantity |
kg |
2.55 |
Pre charged to pipe length |
m |
15 |
Maximum pipe length |
|
m |
30 |
Supply air connection |
|
mm |
348x898 |
Return air connection |
|
mm |
348x898 |
Controller |
|
|
RC-E5, RC-EX3 or
RCN-KIT4-E2 |
Safety pan |
|
|
UA-SP2-E (Optional) |
|
|
|
|